Technical Characteristic
| Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
| 230/240V | 400/415V | 440V | 500V | 690V | |||||||||
| Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
| 0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
| 0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
| 4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
| 6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
| 10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
| 14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
| 18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
| 23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
| 32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
| JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
| 63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
| 80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
| Type | Rated current of trip unit In(A) | Rated current adjustment range (A) | Standard rated power of three-phase motor (kW) | |||||
| AC-3, 50Hz/60Hz | ||||||||
| 230/240V |
400V |
415V |
440V |
500V |
690V | |||
| 0.06 | 0.1-0.16 | - | - | - | - | - | - | |
| 0.25 | 0.6-0.25 | - | - | - | - | - | - | |
| JGV2-32 | 0.4 | 0.25-0.4 | - | - | - | - | - | - |
| 0.63 | 0.4-0.63 | - | - | - | - | - | 0.37 | |
| 1 | 0.63-1 | - | - | - |
0.37 |
0.37 |
0.55 | |
| 1.6 | 1-1.6 | - |
0.37 |
- |
0.55 |
0.75 |
1.1 | |
| 2.5 | 1.6-2.5 | 0.37 |
0.75 |
0.75 |
1.1 |
1.1 |
1.5 | |
| 4 | 2.5-4 | 0.75 |
1.5 |
1.5 |
1.5 |
2.2 |
3 | |
| 6.3 | 4-6.3 | 1.1 |
2.2 |
2.2 | 3 |
3.7 |
4 | |
| 10 | 6-10 | 2.2 | 4 | 4 | 4 |
5.5 |
7.5 | |
| 14 | 9-14 | 3 |
5.5 |
5.5 |
7.5 |
7.5 |
9 | |
| 18 | 13-18 | 4 |
7.5 |
9 | 9 | 9 | 11 | |
| 23 | 17-23 | 5.5 | 11 | 11 |
11 |
11 | 15 | |
| 32 | 24-32 | 7.5 | 15 | 15 |
15 |
18.5 |
26 | |
| JGV3-80 | 40 | 25-40 | - |
18.5 |
- | - | - | 30 |
| 63 | 40-63 | - |
30 |
- | - | - | 45 | |
| 80 | 56-80 | - | 37 | - | - | - | 55 | |
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
| Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
| Power ups | No power | Total | |||
| 1 | 32 | 120 | 2000 | 10000 | 12000 |
| 2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension

Product detail pictures:
Related Product Guide:
It adheres on the tenet "Honest, industrious, enterprising, innovative" to develop new items frequently. It regards buyers, success as its very own success. Let us produce prosperous future hand in hand for New Fashion Design for Overload Circuit Breaker – GV2-M motor protector with overcurrent protection – JUHONG , The product will supply to all over the world, such as: Orlando, Malaysia, Malaysia, Being the top solutions of our factory, our solutions series have been tested and won us experienced authority certifications. For additional parameters and item list details, please click the button to acquire additional nformation.
By Claire from Tajikistan - 2017.09.16 13:44
The factory has advanced equipment, experienced staffs and good management level, so product quality had assurance, this cooperation is very relaxed and happy!
By Anne from Ukraine - 2018.06.03 10:17
Write your message here and send it to us