Dedicated to strict quality management and thoughtful client services, our experienced staff customers are generally available to discuss your demands and guarantee full client pleasure for Electric Contactor, Circuit Breaker, Electric Contactor, Our products are strictly inspected before exporting , So we gain a good reputation all over the world. We looking forward to cooperation with you in the future.
High Quality for Mccb Merlin Gerin - Motor Protector With Overload Protection JGV2 – JUHONG Detail:

Technical Characteristic

Type Rated current of trip unit In(A) Setting current adjustment range (A) Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) Arcing distance (mm)
230/240V 400/415V 440V 500V 690V
Icu Ics Icu Ics

Icu

Ics Icu Ics Icu Ics
0.16

0.1-0.16

100 100 100 100

100

100 100 100 100 100

40

0.25

0.16-0.25

100 100 100 100

100

100 100 100 100 100

40

JGV2-32 0.4

0.25-0.4

100 100 100 100

100

100 100 100 100 100

40

0.63

0.4-0.63

100 100 100 100

100

100 100 100 100 100

40

1 0.63-1 100 100 100 100

100

100 100 100 100 100

40

1.6 1-1.6 100 100 100 100

100

100 100 100 100 100

40

2.5 1.6-2.5 100 100 100 100

100

100 100 100 3 2.25

40

4 2.5-4 100 100 100 100

100

100 100 100 3 2.25

40

6.3 4-6.3 100 100 100 100

50

50 50 50 3 2.25

40

10 6-10 100 100 100 100

15

15 10 10 3 2.25

40

14 9-14 100 100 15 7.5

8

4 6 4.5 3 2.25

40

18 13-18 100 100 15 7.5

8

4 6 4.5 3 2.25

40

23 17-23 50 50 15 6

6

3 4 3 3 2.25

40

32 24-32 50 50 15 6

6

3 4 3 3 2.25

40

JGV3-80 40 25-40 - - 35 17.5 - - - - 4 2

50

63 40-63 - - 35 17.5 - - - - 4 2

50

80 56-80 - - 35 17.5 - - - - 4 2

50

 

Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)

The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)

Type Frame rated current Inm(A) Operating cycles per hour Operation cycle times
Power ups No power Total
1 32 120 2000 10000 12000
2 80 120 2000 10000 12000

Outline and Mounting Dimension

product5


Product detail pictures:


Related Product Guide:

We offer fantastic strength in high quality and enhancement,merchandising,income and marketing and procedure for High Quality for Mccb Merlin Gerin - Motor Protector With Overload Protection JGV2 – JUHONG , The product will supply to all over the world, such as: Colombia, Lesotho, El Salvador, As a well educated, innovative and energetic staff,we are responsible for all elements of the research, design, manufacturing, sales and distribution. With studying and developing new techniques,we are not only following but also leading the fashion industry. We listen attentively to the feedback from our customers and provide instant communication. You will instantly feel our expertise and attentive service.
Wide range, good quality, reasonable prices and good service, advanced equipment, excellent talents and continuously strengthened technology forces,a nice business partner.
5 Stars By Donna from Southampton - 2017.05.21 12:31
The supplier abide the theory of "quality the basic, trust the first and management the advanced" so that they can ensure a reliable product quality and stable customers.
5 Stars By Afra from Italy - 2017.05.02 18:28
Write your message here and send it to us