Good Wholesale Vendors House Circuit Breaker - GV2-M motor protector with overcurrent protection – JUHONG
Good Wholesale Vendors House Circuit Breaker - GV2-M motor protector with overcurrent protection – JUHONG Detail:
Technical Characteristic
| Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
| 230/240V | 400/415V | 440V | 500V | 690V | |||||||||
| Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
| 0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
| 0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
| 2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
| 4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
| 6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
| 10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
| 14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
| 18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
| 23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
| 32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
| JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
| 63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
| 80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
| Type | Rated current of trip unit In(A) | Rated current adjustment range (A) | Standard rated power of three-phase motor (kW) | |||||
| AC-3, 50Hz/60Hz | ||||||||
| 230/240V |
400V |
415V |
440V |
500V |
690V | |||
| 0.06 | 0.1-0.16 | - | - | - | - | - | - | |
| 0.25 | 0.6-0.25 | - | - | - | - | - | - | |
| JGV2-32 | 0.4 | 0.25-0.4 | - | - | - | - | - | - |
| 0.63 | 0.4-0.63 | - | - | - | - | - | 0.37 | |
| 1 | 0.63-1 | - | - | - |
0.37 |
0.37 |
0.55 | |
| 1.6 | 1-1.6 | - |
0.37 |
- |
0.55 |
0.75 |
1.1 | |
| 2.5 | 1.6-2.5 | 0.37 |
0.75 |
0.75 |
1.1 |
1.1 |
1.5 | |
| 4 | 2.5-4 | 0.75 |
1.5 |
1.5 |
1.5 |
2.2 |
3 | |
| 6.3 | 4-6.3 | 1.1 |
2.2 |
2.2 | 3 |
3.7 |
4 | |
| 10 | 6-10 | 2.2 | 4 | 4 | 4 |
5.5 |
7.5 | |
| 14 | 9-14 | 3 |
5.5 |
5.5 |
7.5 |
7.5 |
9 | |
| 18 | 13-18 | 4 |
7.5 |
9 | 9 | 9 | 11 | |
| 23 | 17-23 | 5.5 | 11 | 11 |
11 |
11 | 15 | |
| 32 | 24-32 | 7.5 | 15 | 15 |
15 |
18.5 |
26 | |
| JGV3-80 | 40 | 25-40 | - |
18.5 |
- | - | - | 30 |
| 63 | 40-63 | - |
30 |
- | - | - | 45 | |
| 80 | 56-80 | - | 37 | - | - | - | 55 | |
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
| Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
| Power ups | No power | Total | |||
| 1 | 32 | 120 | 2000 | 10000 | 12000 |
| 2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension

Product detail pictures:
Related Product Guide:
Bear "Customer initially, High quality first" in mind, we do the job closely with our customers and supply them with efficient and skilled providers for Good Wholesale Vendors House Circuit Breaker - GV2-M motor protector with overcurrent protection – JUHONG , The product will supply to all over the world, such as: Albania, Nairobi, Pakistan, Many products fully conform to the most rigorous of international guidelines and with our first-rate delivery service you will have them delivered at any time and in any place. And because Kayo deals in the entire spectrum of protective equipment, our customers don't need to waste time shopping around.