Main Parameters And Technical Performance
● The main technical performance indicators and component equipment of the starter (see Table 1);
● The starter rated control circuit voltage Us is: AC 50/60Hz, 24V, 42V, 110V, 220/230V, 240V,
380/400V, 415V, 440V, 480V, 6OOV;
● Range of action:
○ Pull-in voltage: 50 or 60H 80%Us-110% Us; 50/60Hz 85%Us~110%Us;
○ Release voltage: 20%Us-75%Us
● The operating range of the starter with thermal (overload) relay has the operating characteristics
of thermal relay;
5. The operating frequency with thermal relay is 30 times/hour;
Technical Parameters
Type |
Maximum power AC3 duty(KW) |
Rated current(A) |
Type of enclosure |
Suitable Thermal Relay(A) |
|||||
220V 230V |
380V 400V |
415V |
440V |
500V |
660V 690V |
||||
JLE1-D09 |
2.2 |
4 |
4 |
4 |
5.5 |
5.5 |
9 |
IP42 IP65 |
JLR2-D1312 JLR2-D1314 |
JLE1-D12 |
3 |
5.5 |
5.5 |
5.5 |
7.5 |
7.5 |
12 |
IP42 IP55 |
JLR2-D1316 |
JLE1-D18 |
4 |
7.5 |
9 |
9 |
10 |
10 |
18 |
IP42 IP55 |
JLR2-D1321 |
JLE1-D25 |
5.5 |
11 |
11 |
11 |
15 |
15 |
25 |
IP42 IP55 |
JLR2-D1322 JLR2-D2353 |
JLE1-D32 |
7.5 |
15 |
15 |
15 |
18.5 |
18.5 |
32 |
IP55 |
JLR2-D2355 |
JLE1-D40 |
11 |
18.5 |
22 |
22 |
22 |
30 |
40 |
IP55 |
JLR2-D3353 JLR2-D3355 |
JLE1-D50 |
15 |
22 |
25 |
30 |
30 |
33 |
50 |
IP55 |
JLR2-D3357 JLR2-D3359 |
JLE1-D65 |
18.5 |
30 |
37 |
37 |
37 |
37 |
65 |
IP55 |
JLR2-D3361 |
JLE1-D80 |
22 |
37 |
45 |
45 |
55 |
45 |
80 |
IP55 |
JLR2-D3363 JLR2-D3365 |
JLE1-D95 |
25 |
45 |
45 |
45 |
55 |
45 |
95 |
IP55 |
JLR2-D3365 |
Enclosure |
LE1-D09 and D12 |
Double insulated, protexted to IP 429(3) or to IP 659(4) |
|||||||
LE1-D18 and D25 |
Double insulated, protexted to IP 427(3) or to IP 557(4) |
||||||||
LE1-D32…D95 |
Metal, IP 55 to IP 559 |
||||||||
Control(2 pushbuttons mounted on enclosure cover) |
LE1-D09…D95 |
1 green Start button “I” 1red Stop/Reset button”O” |
|||||||
Connections |
LE1-D32…D95 |
Pre-wired power and control circuit connections |
|||||||
Standard control circuit voltages |
|||||||||
Volts |
24 |
42 |
48 |
110 |
220/230 |
230 |
240 |
380/400 |
440 |
50/60HZ |
B7 |
D7 |
E7 |
F7 |
M7 |
P7 |
U7 |
Q7 |
R |
Shape And Installation Dimensions(mm)
Product detail pictures:





Related Product Guide:
We believe in: Innovation is our soul and spirit. High-quality is our life. Purchaser need is our God for Renewable Design for Vacuum Contactor Switch - Magnetic Starter LE1 Series – JUHONG , The product will supply to all over the world, such as: Cairo, Mali, Estonia, Our focus on product quality, innovation, technology and customer service has made us one of undisputed leaders worldwide in the field. Bearing the concept of "Quality First, Customer Paramount, Sincerity and Innovation" in our mind, We have achieved great progress in the past years. Clients are welcomed to buy our standard products, or send us requests. You will be impressed by our quality and price. Please contact us now!

As a veteran of this industry, we can say that the company can be a leader in the industry, select them is right.