Technical Characteristic
Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
230/240V | 400/415V | 440V | 500V | 690V | |||||||||
Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
Type | Rated current of trip unit In(A) | Rated current adjustment range (A) | Standard rated power of three-phase motor (kW) | |||||
AC-3, 50Hz/60Hz | ||||||||
230/240V |
400V |
415V |
440V |
500V |
690V | |||
0.06 | 0.1-0.16 | - | - | - | - | - | - | |
0.25 | 0.6-0.25 | - | - | - | - | - | - | |
JGV2-32 | 0.4 | 0.25-0.4 | - | - | - | - | - | - |
0.63 | 0.4-0.63 | - | - | - | - | - | 0.37 | |
1 | 0.63-1 | - | - | - |
0.37 |
0.37 |
0.55 | |
1.6 | 1-1.6 | - |
0.37 |
- |
0.55 |
0.75 |
1.1 | |
2.5 | 1.6-2.5 | 0.37 |
0.75 |
0.75 |
1.1 |
1.1 |
1.5 | |
4 | 2.5-4 | 0.75 |
1.5 |
1.5 |
1.5 |
2.2 |
3 | |
6.3 | 4-6.3 | 1.1 |
2.2 |
2.2 | 3 |
3.7 |
4 | |
10 | 6-10 | 2.2 | 4 | 4 | 4 |
5.5 |
7.5 | |
14 | 9-14 | 3 |
5.5 |
5.5 |
7.5 |
7.5 |
9 | |
18 | 13-18 | 4 |
7.5 |
9 | 9 | 9 | 11 | |
23 | 17-23 | 5.5 | 11 | 11 |
11 |
11 | 15 | |
32 | 24-32 | 7.5 | 15 | 15 |
15 |
18.5 |
26 | |
JGV3-80 | 40 | 25-40 | - |
18.5 |
- | - | - | 30 |
63 | 40-63 | - |
30 |
- | - | - | 45 | |
80 | 56-80 | - | 37 | - | - | - | 55 |
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
Power ups | No power | Total | |||
1 | 32 | 120 | 2000 | 10000 | 12000 |
2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension
Product detail pictures:





Related Product Guide:
Our pursuit and firm aim should be to "Always fulfill our buyer requirements". We carry on to produce and structure top-quality excellent solutions for equally our aged and new consumers and accomplish a win-win prospect for our consumers as well as us for PriceList for Contato - GV2-M motor protector with overcurrent protection – JUHONG , The product will supply to all over the world, such as: Karachi, Comoros, Peru, We integrate all our advantages to continuously innovate, improve and optimize our industrial structure and product performance. We will always believe in and work on it. Welcome to join us to promote green light, together we will make a better Future!

This manufacturers not only respected our choice and requirements, but also gave us a lot of good suggestions, ultimately, we successfully completed the procurement tasks.

Write your message here and send it to us