Technical Characteristic
Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
230/240V | 400/415V | 440V | 500V | 690V | |||||||||
Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
Power ups | No power | Total | |||
1 | 32 | 120 | 2000 | 10000 | 12000 |
2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension
Product detail pictures:





Related Product Guide:
With advanced technologies and facilities, strict high-quality handle, reasonable rate, superior services and close co-operation with prospects, we are devoted to furnishing the best price for our customers for High definition Schneider Mpcb - Motor Protector With Overload Protection JGV2 – JUHONG , The product will supply to all over the world, such as: Netherlands, Ukraine, Toronto, All styles appear on our website are for customizing. We meet up to personal requirements with all products of your very own styles. Our concept is to help presenting the confidence of each buyers with the offering of our most sincere service, and the right product.