Technical Characteristic
Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
230/240V | 400/415V | 440V | 500V | 690V | |||||||||
Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
Power ups | No power | Total | |||
1 | 32 | 120 | 2000 | 10000 | 12000 |
2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension
Product detail pictures:





Related Product Guide:
Our merchandise are broadly identified and trusted by end users and can satisfy continually developing economic and social requires for Factory Free sample Smart Circuit Breaker - Motor Protector With Overload Protection JGV2 – JUHONG , The product will supply to all over the world, such as: Jamaica, Germany, Nepal, Our mission is to deliver consistently superior value to our customers and their clients. This commitment permeates everything we do, driving us to continuously develop and improve our products and the processes to fulfill your needs.

Product quality is good, quality assurance system is complete, every link can inquire and solve the problem timely!

Write your message here and send it to us